We designed this 600 AMP T-body deadbreak elbow connector for connecting underground cables to high-voltage equipment like transformers and switchgear. It is fully insulated and submersible, and it complies with IEEE Standard 386. They are compatible with products from other manufacturers that meet this industry standard.
Properties:
Product Type:
600 AMP Deadbreak Elbow Connector
Conductor Size:
24-500 mm2
Insulation Material:
EPDM
Continuous Voltage Rating:
Continuous Voltage Ratings
15kV
25kV
Continuous Operating Voltage
8.7kV / 14.4kV
15.2kV /26.3kV
AC Withstand Voltage
45kV 1min
55kV 5min
DC Withstand Voltage
53kV 15min
78kV 15min
Impulse Withstand Voltage
95kV
125kV
Partial Discharge Voltage <10pC
13kV
22kV
Current Rating:
Current Rating
600 AMP
Heat Stable Current
30kA 2s
Peak Withstand Current
105kA
Selection Guide:
Product No.
Conductor Cross Section (mm2)
Insulated Outer Diameter
Cable Type
Size of Stress Cone
TT-15/630-25
25
16.6
8.7/15
A
TT-15/630-35
35
17.6
8.7/15
A
TT-15/630-50
50
19
8.7/15
A
TT-15/630-70
70
20.6
8.7/15
B
TT-15/63095
95
22.2
8.7/15
B
TT-15/630-120
120
23.6
8.7/15
C
TT-15/630-150
150
25.2
8.7/15
C
TT-15/630-185
185
26.7
8.7/15
C
TT-15/630-240
240
29
8.7/15
D
TT-15/630-300
300
31.2
8.7/15
D
TT-15/630-400
400
34.4
8.7/15
E
TT-15/630-500
500
37.2
8.7/15
F
Product No.
Conductor Cross Section (mm2)
Insulated Outer Diameter
Cable Type
Size of Stress Cone
TT-25/630-35
35
18.6
12/20
B
TT-25/630-50
50
19.6
12/20
B
TT-25/630-70
70
21
12/20
B
TT-25/630-95
95
22.6
12/20
C
TT-25/630-120
120
24.2
12/20
C
TT-25/630-150
150
25.6
12/20
C
TT-25/630-185
185
27.2
12/20
D
TT-25/630-240
240
28.7
12/20
D
TT-25/630-300
300
31.1
12/20
E
TT-25/630-400
400
33.2
12/20
E
Scope of delivery:
Part Name
Number
T-body Elbow Connector:
3
Insulator:
3
Conductor Cable Lug:
3
Adaptor (stress cone):
3
Double-headed bolt:
1
Silicone Grease:
1
Assembly instructions:
1
Accessories
If you have any other special requirements, please contact our sales engineer.